IST-D Isolated Signal Transmitter
ISC Dual Channel Isolated Signal Conditioner/Converter
VT9621 Fuzzy Enhanced PID Dual Channel Controller

 
 
 
 
 
 
 
 
You are   visitors
 
Home > Produtos > Transmitters & Converters > i SignalCon
   

A Programmable & user-friendly converter, was born.
ISC Dual Channel Isolated Signal Average Conditioner/Converter

 

 

Feature:
Programmable for various input signals,
   measuring rang
e
Configurable without external Loop Power Connected.
Input :
Resistance thermometer (Pt100)
Thermocouple (J,K,T,E,B,R,S,N,C)
Voltage/Current (mV/V/mA)

The unique Math function:

   PV1 ¡G Input 1 ; PV2 ¡G Input 2
   A ¡A B ¡A C ¡G Constant Factors are set by user
   When Average ( ¡Ò ) function is selected, calculation    formula is as followings

   PV1¡GInput 1
   PV2¡GInput 2
   A¡AB¡AC : Constant Factor A¡AB¡AC can be defined according to application.C¡Ú0; ,
¡Ô : disable
Output device:
   1.ISC-S : Single Analog Output: 4 ~20 mA¡B0~10VDC¡K
   2.ISC-D: Dual Analog Outputs: 4 ~20 mA¡B0~10VDC       ¡K
   3.ISC-C : One Analog Output(OUT1) 4 ~20 mA¡B       0~10VDC ¡K with    RS485 Com port : MODBUS-
      RTU(OUT2)
High accuracy in total ambient temperature range.
Fault signal on sensor break presettable.

   
 
The Din Rail converter is user configurable with the software and interface cable URC-1020 or handheld programmer.
The is user-friendly software. The latest release version can be download free from website.
Interface cable consist of interface converter and USB plug. It can be purchased separately from supplier. During configuration the converter can work alone without connecting to a power source.
 
 
Specification:
   
 
Input Thermocouple (T/C) : industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90).
Pt100: Excitation 180uA. 2 or 3 wire connection (ITS-90 £\ =0.00385).
Voltage: -60mVdc to 60mVdc or ¡V10Vdc to 10Vdc.
Current : 0-24mAdc
Accuracy Refer to Table 1 Input Signal
A/D Resolution 16 bits
Input Sampling Rate <200ms
Power Supply DC 24V
Output Current Output: 4~20mA( Resistive load 600£[ max.)
Continuous Voltage Output: 0~50mV; 0~10V¡K( Resistive load 600£[ min.)
Output Resolution 0.6 £g A(15 bits)
Output Response Time <200ms
Common Mode Rejection Ratio(CMRR) >80dB
Electromagnetic Compatibility (EMC) En 50081-2, En 50082-2
Galvanic isolation 4 KV. between input and output
Operating Temperature -40 to 85 ¢X C
Humidity 0 to 90% RH
Dimension 75mm(W)x87mm(H)x18.5mm(D)
 
Table 1 Input Signal
Input signal Maximum Range Accuracy
Thermocouple J -50 to 1000 ¢X C (-58 to 1832 ¢X F ) ¡Ó 1 ¢X C
Thermocouple K -50 to 1370 ¢X C (-58 to 2498 ¢X F ) ¡Ó 1 ¢X C
Thermocouple T -270 to 400 ¢X C (-454 to 752 ¢X F ) ¡Ó 1 ¢X C
Thermocouple E -50 to 960 ¢X C (-58 to 1760 ¢X F ) ¡Ó 1 ¢X C
Thermocouple B 0 to 1750 ¢X C (32 to 3182 ¢X F ) ¡Ó 2 ¢X C (Note1)
Thermocouple R -50 to 1750 ¢X C (-58 to 3182 ¢X F ) ¡Ó 2 ¢X C
Thermocouple S -50 to 1750 ¢X C (-58 to 3182 ¢X F ) ¡Ó 2 ¢X C
Thermocouple N -50 to 1300 ¢X C (-58 to 2372 ¢X F ) ¡Ó 2 ¢X C
Thermocouple C -50 to 1800 ¢X C (-58 to 3272 ¢X F ) ¡Ó 2 ¢X C
Pt100 -200 to 600 ¢X C (-328 to 1112 ¢X F ) ¡Ó 0.2 ¢X C
mV -60mVto 60mV ¡Ó 0.01m V
Voltage (Note2) -10 to 10Vdc ¡Ó 1m V
Current (Note2) 0 to 24mAdc ¡Ó 10£gA
 
Note 1 : Accuracy is not guaranteed between 0 and 400¢XC (0 and 752¢XF) for type B.
Note 2 : The internal DIP switch should be set.
 
 
Dimension:
 

 

 
 
Wiring Diagram:
 
 
 
Ordering Infomation: