Multi-channels Module type PID Controller (MMC)

SD 430 Microprocessor Indicator

MPC Microprocessor Based Module Type PID Controller

 
 
 
 
 
 
 
 
You are   visitors
 
Home > Products > Transmitters & Converters > i SignalCon
   

ISC 2-Channel Isolated Universal Signal Converter/Conditioner/Isolator

 

Feature:
Both channels must be set to same input type
The unique Math function

    PV1,PV2 is the measuring value of Channel 1 and
    Channel 2 separately. A,B,C is a constant set by user
The unique High/Low comparison output
   The output 1 can scale to PV1 or PV2 whichever is
    higher/lower than the other
Programmable for various input signals and measuring
    range
Configurable without Power Connected
Full 3-way isolation for 1500 Vrms
DIN rail mount
Dual channel Input
   Resistance thermometer (Pt100)
   Thermocouple (J,K,T,E,B,R,S,N,C)
   Voltage/Current transmitter (mV/V/mA)
Dual 0/4 to 20 mA or 0~10V analogue output (ISC-D)

RS485 communication interface with Modbus RTU
    protocol (ISC-C)

Fault signal on sensor break presettable

   
 

The Din Rail converter is user configurable using our software on your PC/notebook or our dedicated handheld programmer. The easy to use software is available free from your supplier or can be downloaded from our web site and should be used in conjunction with the URC-1020 USB cable which incorporates an interface converter necessary for communications.The ISC converter can be configured without any loop or power connected making it easy to configure in the workshop before installation.

 
 
Specification:
   
 
Input Thermocouple (T/C) : industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90).
Pt100: Excitation 180uA. 2 or 3 wire connection (ITS-90 £\ =0.00385).
Voltage: -60mVdc to 60mVdc or ¡V10Vdc to 10Vdc.
Current : 0-24mAdc
Accuracy Refer to Table 1 Input Signal
A/D Resolution 16 bits
Input Sampling Rate <200ms
Power Supply DC 16~32V
Power Consumption 1.7W (max)
Output Current Output: 4~20mA( Resistive load 600£[ max.)
Continuous Voltage Output: 0~50mV; 0~10V¡K( Resistive load 600£[ min.)
Output Resolution 0.6 £g A(15 bits)
Output Response Time <200ms
Common Mode Rejection Ratio(CMRR) >80dB
Electromagnetic Compatibility (EMC) En 50081-2, En 50082-2
Galvanic isolation 2.8 KV. between input and output
Operating Temperature -10 to 50 ¢X C
Humidity 0 to 90% RH
Dimension 75mm(W)x87mm(H)x18.5mm(D)
 
Table 1 Input Signal
Input signal Maximum Range Accuracy
Thermocouple J -50 to 1000 ¢X C (-58 to 1832 ¢X F ) ¡Ó 1 ¢X C
Thermocouple K -50 to 1370 ¢X C (-58 to 2498 ¢X F ) ¡Ó 1 ¢X C
Thermocouple T -270 to 400 ¢X C (-454 to 752 ¢X F ) ¡Ó 1 ¢X C
Thermocouple E -50 to 700¢XC (-58 to 1292¢XF) ¡Ó 1 ¢X C
Thermocouple B 0 to 1750 ¢X C (32 to 3182 ¢X F ) ¡Ó 2 ¢X C (Note1)
Thermocouple R -50 to 1750 ¢X C (-58 to 3182 ¢X F ) ¡Ó 2 ¢X C
Thermocouple S -50 to 1750 ¢X C (-58 to 3182 ¢X F ) ¡Ó 2 ¢X C
Thermocouple N -50 to 1300 ¢X C (-58 to 2372 ¢X F ) ¡Ó 2 ¢X C
Thermocouple C -50 to 1800 ¢X C (-58 to 3272 ¢X F ) ¡Ó 2 ¢X C
Pt100 -200 to 600 ¢X C (-328 to 1112 ¢X F ) ¡Ó 0.2 ¢X C
mV -60mVto 60mV ¡Ó 0.01m V
Voltage (Note2) -10 to 10Vdc ¡Ó 1m V
Current (Note2) 0 to 24mAdc ¡Ó 10£gA
 
Note 1 : Accuracy is not guaranteed between 0 and 400¢XC (0 and 752¢XF) for type B.
Note 2 : The internal DIP switch should be set.
 
 
Dimension:
 
 
 
Wiring Diagram:
 
 
 
Block Diagram:

 
 
Ordering Information:
 

The standard unit is supplied set for thermocouple/PT100 inputs.
The converters are otherwise user configurable.