| Input |
Thermocouple
(T/C): J, K,
T, E, B, R,
S, N, C (ITS-90)
|
| Pt100:
Excitation 180uA.
2 or 3 wire
connection (ITS-90
£\=0.00385) |
| Voltage:
-60mVdc to 60mVdc
or -10Vdc to
10Vdc |
| Current:
0mA to 24mA |
| Sampling
Rate |
100mS |
|
Control
Mode |
Proportional
Band: 0.0~300.0%
(0.0 %=On/Off
mode) |
| Integral
Time: 0~3000
sec |
| Derivative
Time: 0~1000
sec |
| Hysteresis:
0.0~999.9 or
0~9999 |
| Cycle
Time: 1~60 sec |
|
Control Output |
Relay
Contact Output:
5A/240 VAC (Rasistive
load) |
|
Pulsed Voltage
Output: DC 0/24V
(Rasistive load
250 £[ Min.) |
| Alarm
Output |
Relay Contact
Output: 5A/240
VAC (Rasistive
load) |
|
General Specifications
|
Power supply:
Universal 90
~ 265 VAC 50/60
Hz |
| Power
consumption:
4VA Max. |
|
Aux. 24Vdc power
output: 25mA
(max.) |
| Common
mode rejection
ratio: >80dB |
| Operating
temperature:
0 to 50¢XC |
| Humidity:
0 to 85% RH
(Non-Condense
Condition) |
|
Electromagnetic
compatibility
(EMC): En 50081-2,
En 50082-2 |
|
Housing material:
ABS plastic.
UL 94V0 |
|
Weight: 100g
|
|
Digital
Communication
|
EIA RS-485 with
ModBus RTU mode
Protocol |
|
Baud Rate: 2400,4800,9600,19200
bps |
|
1 Start bit,
8 Data bits,
None Parity,
2 Stop bits
|